- The electrical power demand: this is the power demand expected from a generator in kW and kVA. Special loads as motors, UPS, helium lighting, electric furnaces or others should be mentioned.(1)Base load Power: Power available for continuous full load operation. An overload of 10% permitted for one hour in every twelve hours of operation.(2)Prime Power: Power available at variable load in lieu of main power network. An overload of 10% permitted for one hour in every twelve hours of operation.(3)Standby Power: Power available at a variable load in the event of a main power network failure up to a maximum of 500 hours per year. No overload is permitted.
- Duty of operation: this is could be of three modes of operation:
- Rated voltage. It depends on where you are located.
- Rated frequency. It depends on where you are located.
- Number of phases. It is either single phase (two wires) or three phase (four wires). It depends on equipment you have. You can check this info from your mains energy meter.
- Manual Start or Auto Start. This info shows the engine response after failure of mains (national grid). Shall this be manually done through operators or automatically through an automatic transfer switch (ATS) linked to the Genset controller?
- Site Conditions. This includes the max and min temperatures, altitude above sea level, relative humidity and dust.
- Sound level. If Genset will be placed in residential areas, the sound of generator will be very noisy and should be proofed. Check our canopy section for more info.
- Exhaust Emissions compliance. This depends on what type of emissions legislations are applied in your country. Check Perkins emissions guide.
Other Features
You can check our standard features through leaflets for Genset
and control panels. If other features are requested, check the option section
in control panel leaflet or contact our sales dept.
What is the
cheapest way to maintain my generator and increase its lifetime?
Follow the recommendations of the preventive maintenance schedule
and carry out a daily visual inspection.
The visual
inspection should only take a few minutes. When time is taken to perform these
checks, costly repairs and accidents can be avoided. For maximum engine service
life, make a thorough inspection of the generating set compartment before
starting the engine. Look for items such as oil leaks or coolant leaks, loose
fastening, worn belts, loose connections and debris buildup.
Clean,
repair or renew, as necessary. Refer to operation manuals and / or Assembly
& Dismantling Manual and follow all relevant safety precautions. Always
clean fluid leaks in accordance with local regulations to prevent
contamination. For any type of leak (coolant, lubrication, or fuel oil) clean
up the fluid.
If leakage
is observed, find the source and correct the leak. If a leak is suspected,
check the fluid levels more often than recommended until the leak is found or
repaired.
Warning! Accumulated grease and / or oil
on an engine or floor are a fire hazard. Remove any debris by steam cleaning or
by using high pressure water.
- All guards must be fitted in their correct places. Repair or renew damaged or missing guards.
- Wipe all caps and plugs before the engine is serviced in order to reduce the chance of contamination.
- Check the condition of all coolant pipes. Ensure that they are correctly installed, clamped and tight.
- Inspect the coolant pump for coolant leaks. Note: The coolant pump seal is lubricated by coolant in the coolant system. It is normal for a small amount of leakage to occur as the engine cools down and parts contract. Excessive coolant leakage may indicate the need to renew the coolant pump seal.
- Inspect the radiator and heater radiator (if fitted) for damaged, bent or broken fins, corrosion, dirt, grease, insects, leaves, oil and other debris.
- Inspect the lubrication system for leaks at the front crankshaft seal, the rear crankshaft seal, the oil sump, the oil filters and the valve cover.
- Inspect the fuel system for leaks. Look for loose or damaged fuel lines.
- Drain the water and sediment from the fuel tanks and water/fuel separator filter on daily basis; ensure that only clean fuel enters the fuel system.
- Inspect the air inlet system. Ensure ducts are clear of restriction. Look for elbow cracks and loose clamps. Check that hoses and tubes are not in contact with other hoses, tubes, wiring harnesses, etc.
- Check that the Fan and accessory drive belts are fitted to the correct tension. Inspect the belts for cracks, breaks or other damage. Note: Where more than one belt is used between pulleys, it is important that all belts are renewed together.
- Inspect all wires and wiring harnesses for loose connections. Make sure all electrical connections are clean and tight. Also look for worn or frayed wires and renew if necessary.
- Check that all ground straps are in good condition. Ensure that the ground straps and joint faces are clean and tight.
- Disconnect any battery charges which are not protected against the current drain of the starter motor.
- Check the condition of the electrolyte level of the batteries, unless maintenance free batteries are fitted.
- Ensure that the battery is at full charge and that all connections are clean and tight.
- Check the condition of the Genset controller, gauges and meters on control panel. Renew those that are damaged, cracked or that cannot be calibrated.
- Check the condition of the alternator air flow; blocked air-inlet or air-outlet. Also check the alternator cooling fan for any crack.
- Check the condition of the anti-vibration mountings for any deterioration or non-tightened screws.
- Check the condition of the circuit breaker and its box for any damage.
- Check the condition of the power and control cables for any damage, short/open circuit or loose connections.
How can I get preventive
maintenance schedule of my generator?
It should be
attached with genset catalogs. Whatever the case,Feel free to contact our
service department (lashari@damaan.com.pk)
When do I have to change the Air
filters?
According to
preventive maintenance schedule, it is recommended that the air filters must be
changed every one year of operation. You can check the air cleaner service
indicator connected to Filter housing to see if there is restriction in the air
filter.
When do I have to change the lube
oil and oil filters?
The time
interval for changing the lube oil and oil filters is found in the maintenance
schedule which may differ depending on engine type and sulfur content of fuel.
How can I have my generator ready
to take load?
This is dependent on two main factors:
- Your commitment to preventive maintenance.
- The engine temperature must always be above 25C. If the engine is placed in a very cold environment, you may need to have engine heaters.
What is the minimum load that the
engine must be operated?
The minimum Load that an engine must be operated must not be less
than 25-30% of its rated output.
What is the risk if engine load
is less than the minimum?
If an engine
is operated on a load less than the minimum, certain symptoms of high
Lubrication oil consumption and oil leaks may be observed. The cylinder
temperatures are too low to insure complete burning of all the fuel delivered.
A further result is that of abnormal carbon built up on the valves, piston
crowns and exhaust ports. Thus the normal service interval of overhauls may be
reduced.
What are the available types of
Generator sets (Gensets)?
Gensets are
mainly fitted with either diesel, gasoline or gas engines.
What are the most common
definitions and deliverables that customers expect from a Genset?
They expect
measurable power density, load acceptance, emissions, fuel consumption and noise.
Power density measures the rating over the volume of the engine; the higher the
power density is the more effective the Genset can be. Load Acceptance –
Gensets are often used for standby/emergency power, where they will be expected
to start-up, run up to running speed and then accept a large % of maximum
electrical load.
Load
acceptance is measured in terms of a % frequency dip and a recovery time, and
is defined by ISO 8528-5 and NFPA 99/110. Additional requirements are customer
driven demanding typically 80% of the prime rating within 10 seconds of
start-up, within ISO 8528-5 limits. Engine load acceptance has been
demonstrated as a linear function of trapped mass.
Generator Class
|
||
Frequency Criteria
|
G2
|
G3
|
Steady State Frequency Band (%)
|
1.5
|
0.5
|
Transient Deviation On Load Increase (%)
|
10.0
|
7.0
|
Transient Deviation On Load Decrease (%)
|
10.0
|
10.0
|
Recovery Time (s)
|
5
|
3
|
Steady State Tolerance Band
|
2.0
|
2.9
|
Emissions-
Genset emissions are complicated and specific to the country in which they
operate. Generally requirements are less demanding than other off highway
equipment, but are often driven by marketing rather than legislative needs.
Legislative limits are complicated, determined by introduction date, engine
powers and power rating. The three most important limits are listed below with
links to sites where full documentation can be found.
European Limits (Directive 97/98/EC)
Commonly referred to as EU Stage ‘X’ Emissions
www.dieselnet.com/standards/eu/offroad.html
North American Limits (Federal Regulations 40 CFR Part 89)
Commonly referred to as EPA Tier ‘X’ Emissions
www.dieselnet.com/standards/us/offroad.html
TA LUFT
Legislation
|
Power
|
NOx g/Nm3
|
SO2 g/Nm3
|
CO g/Nm3
|
PM g/Nm3
|
HC g/Nm3
|
TA Luft
(1986)
|
< 3 MWth
|
4.0
|
-
|
0.65
|
0.13
|
0.15
|
³ 3 MWth
|
2.0
|
-
|
0.65
|
0.13
|
||
½ TA Luft
|
< 3 MWth
|
2.0
|
-
|
0.65*
|
0.13
|
0.15
|
³ 3 MWth
|
1.0
|
-
|
0.65*
|
0.13
|
0.15
|
* Sometimes 0.325 g/Nm3Perkins
emissions brochure:
http://www.perkins.com/cda/components/securedFile/displaySecuredFileServletJSP?fileId=286181&languageId=7
Fuel
Consumption- Each Genset should carry a specs sheet that details the fuel
consumption levels according to load percentages and frequency.
Noise Levels-
Gensets could be sold either as open sets or coupled with sound proof canopies.
Each type of canopy with specific design delivers a certain level of sound
attenuation measured by dBa (Decibels).
What is a Genset and how does it
differ to the industrial engine on which most are based?
The
following list sets out to explain many of the basic terms applicable to Genset
design, development and ownership.
Electrounit – A fixed speed diesel engine with
ratings to suit a Genset application. Comes complete with radiator, cooling
group and fan.
Electropak – An Electrounit without radiator,
cooling group and fan. Suitable for individually installed Combined Heat &
Power setups.
IOPU – Independent Operating Power
Unit. These are multi speed non vehicle power units. They are normally sold
with radiator, cooling group and fan, and typically share ratings from their
off highway derivatives. Typical applications include pumps and compressors.
Operating Speed – Gen-sets are normally governed
to fixed speed running. 1500 rpm to produce 50Hz electrical supply for European
market and 1800 rpm to produce 60 Hz for US market. 60Hz supply can be achieved
at 1200Hz with some alternator sets– this is uncommon.
KWe – Kilowatts electrical is a
measure of electrical power produced by a Genset. 60Hz generator sets are
usually marketed in terms of kWe.
KVa – Kilovolt amps is a measure of
electrical power produced by a Genset. 50Hz Gensets are usually marketed in
terms of kVa. As Gensets produce an alternating current P=VI doesn’t hold true.
Voltage and current follow sinusoidal wave forms with a phase shift due to the
reactance (generated by inductance & capacitance) of the load on the
alternator, and hence a power factor is used. Industry assumes a 100% resistive
load for which a 0.8 power factor is used. This relates kWe to kVa by the
following:
kWe = kVa x 0.8
Marketing – As a general rule of thumb, a
Genset will produce X kVa at 50Hz and X kWe at 60Hz. So we owe the confusing
nomenclature to marketing who would like to sell, for example, a 100kVa
(50Hz)/100kWe (60Hz) Genset.
Fuel Coolers – Gen-sets are normally fitted
into a frame, which holds a small fuel or “day tank” for limited time running.
If the Genset operates in elevated ambient temperatures, or the engine has a high
fuel spill ratio, the temperature of the fuel will often be controlled by a
small fuel cooler (air-to-fuel) mounted on the cooling group. The cooler
prevents rises in “day tank” temperatures preventing fuel injector damage.
Fans – All Electrounits are fitted
complete with fans to provide cooling to the radiator and charge cooler if
fitted. Two versions of fans are normally offered for Gensets and IOPU’s,
pushers (which blow air through the radiator) and pullers (which pull air
through the radiator). The customer is able to specify the type most relevant
to their application/installation. The type of fan used will affect the ambient
air temperature the bulk of the engine will see, and may have consequences on
the engines rating and performance.
Fan Power (Fp) – Depending on the size of the
Genset, the power required to drive the fan will vary between 10% for smaller
Gensets (<10L) and 5% for larger Gensets (>10L).
Alternator Efficiency (ha) – The alternator on the Genset
converts the mechanical energy delivered by the engine into electrical energy,
and has an associated efficiency. Typically alternators have an efficiency of
0.95 (95%).
kWm – Gen-sets are marketed in terms
of the electrical power which they produce. However engine manufacturers are
more interested in the mechanical power which their engine needs to deliver to
the alternator to provide the quoted electrical power. This includes fan powers
and alternator efficiency:
kWe = (kWm –Fp) x ha or kWe = kWm
x 0.90 x 0.95 ( <10L engine)
kWe = (kWm –Fp) x ha or kWe = kWm
x 0.95 x 0.95 (>10L engine)
Ambient/Altitude
Clearance - Gen-sets are operated in global environments, with extreme ambient
and altitude operating environments. Running at higher ambient temperatures
adds additional loads on the cooling system, and at elevated altitudes the
inlet system struggles to deliver sufficient air for combustion with the lower
air density/pressure. Gen-sets are expected to run at altitudes up to 4000m and
ambient temperatures of 55 ⁰C, which may require derate.
Clearance is
defined as the margin on the altitude/ambient performance limiting parameters
(such as coolant and exhaust temperature) when tested at standard operating
conditions (sea level 25 ⁰C). From the Ambient/Altitude clearance, curves are
developed to assist application engineers in sizing appropriate derate for
extreme operating conditions.
Power Rating - Gen-sets are sold at three main
power ratings determined by their application. Power ratings are defined by ISO
8528-1. Generic power ratings are summarised below:
Rating
Summary
Standby Power
Typically
100% of maximum permissible power.
100% load
factor of published standby power.
No overload
capability.
Maximum
usage of 500 hours per year.
Maximum 300
hours continuous running.
Prime Power
Typically
91% of maximum permissible power.
Mean load
factor of 80% published prime power
over 24hour
period.
10 %
overload for 1 hour in 10.
Unlimited
running.
Baseload Power (Continuous)
Typically
70% of maximum permissible power.
100% load
factor of published baseload power.
10 %
overload for 1 hour in 10.
Unlimited running.
Governing – Gen-sets are fixed speed
applications with governors developed to maintain the desired running speed
within careful limits. This is particularly important as electrical equipment
powered by the Genset may be damaged by supply outside of the normal 50/60Hz
limits. Gen-set governing is detailed by ISO 8528.
0 Reviews:
Post Your Review